Dimensions W x L x H |
(incl. interlinking block and connection system)50 mm x 107 mm x 50 mm |
No. of outputs |
2 |
Diagnostics |
Wire break per channelLimit value violation per channelOutput signal short circuit per channelActuator supply short circuitParameterization errorUndervoltage of outputs |
Parameterization |
Data formatFail-safe modes per channelForcing per channelLimit value monitoring per channelIdle mode per channelMeasured value smoothingSignal range per channelResponse to short circuitWire break monitoring per channel |
LED indicators |
1 group diagnostics |
Internal cycle time |
4 ms |
Repetition accuracy |
0.05 % at 25 °C |
Fuse protection (short circuit) |
Internal electronic fuse |
DC operating voltage range |
18 V … 30 V |
Intrinsic current consumption at nominal operating voltage |
Typ. 100 mA |
Operating error limit related to the ambient temperature range |
±0.6 % |
Basic error limit at 25°C |
±0.5 % |
Nominal operating voltage DC |
24 V |
Electrical isolation between channel and internal bus |
Yes, without using the internal sensor supply |
Electrical isolation between channels |
no |
Corrosion resistance class (CRC) |
1 – Low corrosion stress(when installed) |
Storage temperature |
-20 °C … 70 °C |
Degree of protection |
Depends on manifold block |
Ambient temperature |
-5 °C … 50 °C |
Product weight |
49 g |
Data format |
12 bit + signScalable to 15 bits |
Max. cable length |
30 mShielded |
Sensor type |
0 – 10 V0 – 20 mA4 – 20 mA |
Housing material |
PA-reinforcedPC |