Dimensions W x L x H |
18.9 mm x 76.6 mm x 124.3 mm |
Width dimension |
18.9 mm |
No. of inputs |
4 |
Diagnostics via LED |
Faults per channelFaults per module |
Diagnostics via bus |
Wire breakSensor supply short circuit/overloadParameter errorParameterization errorOverload at analog inputsUpper limit value violatedUnderflow/overflowLower limit value not complied with |
Measured variable |
VoltageCurrent |
Module parameters |
Analog input data formatSensor supply short circuit diagnosticsParameterization error diagnosticsAnalog input overload diagnosticsLimit monitoring hysteresisDeactivate sensor supplyResponse to analog input overloadResponse to short circuit/overload |
Channel parameters |
Wire break diagnosticsParameter error diagnosticsUnderflow/overflow diagnosticsUpper limit diagnosticsLower diagnostic limitSmoothing factorSignal range per channelLower/upper limit |
Repetition accuracy |
±0.1 % at 25 °C |
Fuse protection (short circuit) |
Internal electronic fuse per module |
Intrinsic current consumption at nominal operating voltage for electronics/sensors |
Typically 70 mA |
Operating error limit related to the ambient temperature range |
±0.3 % |
Basic error limit at 25°C |
±0.2 % |
Max. residual current of inputs per module |
1.4 A |
Nominal operating voltage DC for electronics/sensors |
24 V |
Power failure buffering |
10 ms |
Electrical isolation between channel and internal bus |
yes |
Electrical isolation between channels |
no |
Permissible voltage fluctuations for electronics/sensors |
± 25 % |
Certification |
RCM compliance markc UL us – Listed (OL) |
KC characters |
KC EMC |
CE marking (see declaration of conformity) |
As per EU EMC directive |
Certificate issuing authority |
UL E239998 |
Vibration resistance |
Transport application test with severity level 1 as per FN 942017-4 and EN 60068-2-6 |
Shock resistance |
Shock test with severity level 1 as per FN 942017-5 and EN 60068-2-27 |
Corrosion resistance class (CRC) |
0 – No corrosion stress |
Storage temperature |
-20 °C … 70 °C |
Relative air humidity |
95 %Non-condensing |
Degree of protection |
IP20 |
Ambient temperature |
-5 °C … 50 °C |
Note on ambient temperature |
-5 – 60 °C for vertical installation |
Product weight |
96 g |
Max. address capacity inputs |
8 byte |
Signal range |
-10 – 10 V-20 – 20 mA-5 – 5 V0 – 10 V0 – 20 mA1 – 5 V4 – 20 mA |
Data format |
15 bit + signLinear scaling |
Max. cable length |
30 mShielded |
Electrical connection input, function |
Analog input |
Electrical connection input, connection type |
4x terminal strip |
Electrical input connection, connection technology |
Spring-loaded terminal |
Electrical connection, input, number of pins/wires |
4 |
Electrical connection for input, conductor cross section |
0.2 mm² … 1.5 mm² |
Electrical connection for input, information on conductor cross section |
0.2 – 2.5 mm² for flexible conductors without cable end sleeves |
Electrical connection input 2, function |
Functional ground |
Electrical connection input 2, connection type |
Terminal strip |
Electrical input 2 connection, connection technology |
Spring-loaded terminal |
Electrical connection, input 2, number of pins/wires |
4 |
Electrical connection for input 2, connection pattern |
00995842 |
Electrical connection for input 2, conductor cross section |
0.2 mm² … 1.5 mm² |
Electrical connection for input 2, information on conductor cross section |
0.2 – 2.5 mm² for flexible conductors without cable end sleeves |
Type of mounting |
With H-rail |
Note on materials |
Contains paint-wetting impairment substancesRoHS-compliant |
Housing material |
PA |
Reviews