Electrical data
| Operating voltage [V] | 18…30 DC; (“supply class 2” to cULus) |
|---|---|
| Current consumption [mA] | 50 |
Sensor supply US
| Current rating per port [A] | 0.1 |
|---|
Inputs / outputs
| Number of inputs and outputs | Number of digital inputs: 8 |
|---|
Inputs
| Number of digital inputs | 8; (4 x 2) |
|---|---|
| Input circuit of digital inputs | PNP |
| Input current limitation [mA] | 15 |
| Input current High [mA] | 6…10 |
| Input current Low [mA] | 0…2 |
| Switching level high [V] | > 11 |
| Digital inputs protected against short circuits | yes |
Interfaces
| Communication interface | IO-Link | ||||
|---|---|---|---|---|---|
| Supported DeviceIDs |
|
IO-Link Device
| Transmission type | COM2 (38,4 kBaud) |
|---|---|
| IO-Link revision | 1.1 |
| SDCI standard | IEC 61131-9 |
| SIO mode | no |
| Process data binary | 32 |
| Min. process cycle time [ms] | 2.9 |
Operating conditions
| Ambient temperature [°C] | -25…70 | ||||
|---|---|---|---|---|---|
| Storage temperature [°C] | -25…85 | ||||
| Max. relative air humidity [%] | 90; (non condensing) | ||||
| Protection | IP 67 | ||||
| Protection rating (NEMA 250) | 6P | ||||
| Chemical media |
|
Tests / approvals
| EMC |
|
|---|
Mechanical data
| Weight [g] | 144.5 |
|---|---|
| Materials | PBT; socket: brass nickel-plated; O-ring: FKM |
| Sealing material | FKM |
Displays / operating elements
| Display |
|
|---|
Accessories
| Items supplied |
|
||
|---|---|---|---|
| Accessories (optional) |
|
Remarks
| Remarks |
|
|||
|---|---|---|---|---|
| Pack quantity | 1 pcs. |
Electrical connection – IO-Link
| Connector: M12; coding: A |
Electrical connection – Process connection
| Connector: M8; coding: A; Sealing: FKM |