Description
Description
Construction features
• Compressor: hermetic, rotary scroll type, complete with thermal protection and casing heater. 3 capacity steps with high efficiency at partial loads for models 245-265.
• Water side heat exchanger: adequately insulated stainless steel plates, complete with antifreeze heater and water flow differential pressure switch.
• Air side heat exchanger: finned coil with copper pipes and aluminium fins, complete with protection grilles.
• Fan: external rotor helical type electric fan equipped with internal thermal protection, accident protection grilles and proportional electronic device for continuous fan speed regulation.
• Control: microprocessor electronic control with Adaptive Function Plus logic.
• Structure: made of galvanised and painted sheet steel.
• The unit is also complete with:
– Master/Slave control up to 4 units in parallel;
– clock board.
Models
• TCAEY: unit designed for cooling only.
• THAEY: heat pump unit.
PUMP set-up
• Pump unit complete circulator, single or double electric pump, including an automatic actuation pump in standby (mod. 245-265), expansion tank, air bleed valves, safety valve and water side pressure gauge.
TANK&PUMP set up
• Pump unit complete inertial buffer tank, circulator, single or double electric pump, including an automatic actuation pump in standby (mod. 245-265), expansion tank, air bleed valves, safety valve and water side pressure gauge.
Factory fitted accessories
• Soft-start device.
• Silenced set up.
• Desuperheater.
• 100% heat recovery unit.
• Condensing control with fans with EC motor.
• Refrigerant circuit high and low pressure gauges (mod. 245-265).
• Buffer tank antifreeze heater.
• Electric pump antifreeze heater (mod. 245-265).
• Forced limit of power consumption.
• Refrigerant leak detector.
• Digital input for double set-point
• 4-20 mA analogue signal for shifting set-point.
• Energy parameter measuring device.
• Low water set-point temperature.
• Pre-painted copper/coils or copper/copper coils.
Separately supplied accessories
• Outdoor air temperature probe for set-point compensation.
• Additional electrical resistance for heat pump, managed by regulation.
• Rubber anti-vibration mounts.
• Water filter.
• Remote keypad with display.
• Interfaces for serial communication with other devices.
• Serial converter (RS485/USB).
• Rhoss supervisors for unit monitoring and remote management.
Technical data
| TCAEY MODEL (P1 set up) | 233 | 238 | 245 | 250 | 260 | 265 | ||
| ❶ | Cooling capacity | kW | – | 39,4 | 44,8 | 51,9 | 59,8 | 64,6 |
| ❶ | Absorbed power | kW | – | 12,83 | 17,43 | 19,73 | 22,15 | 24,01 |
| ❶ | E.E.R. | – | 3,07 | 2,57 | 2,63 | 2,7 | 2,65 | |
| THAEY MODEL | ||||||||
| ❷ | Heating capacity | kW | 37,8 | 42,1 | 48,1 | 56,2 | 62,6 | 68,3 |
| ❷ | Absorbed power | kW | 12,54 | 13,19 | 16,82 | 18,97 | 20,86 | 23,71 |
| ❷ | C.O.P. | 3,01 | 3,19 | 2,86 | 2,96 | 3 | 2,88 | |
| ❶ | Cooling capacity | 32,3 | 38,5 | 42,3 | 50,3 | 57,8 | 61,6 | |
| ❶ | E.E.R. | 2,59 | 2,95 | 2,49 | 2,68 | 2,64 | 2,54 | |
| TCAEY-THAEY MODEL | 233 | 238 | 245 | 250 | 260 | 265 | ||
| ❸ | Sound pressure | dB(A) | 54 | 54 | 56 | 56 | 57 | 57 |
| ❸ | Silenced setup sound pressure | dB(A) | 51 | 51 | 53 | 53 | 54 | 54 |
| Scroll compressors/steps | n. | 2/2 | 2/2 | 2/3 | 2/3 | 2/3 | 2/3 | |
| Circuits | no. | 1 | 1 | 1 | 1 | 1 | 1 | |
| Buffer tank water content (TANK&PUMP) | l | 80 | 150 | 150 | 150 | 150 | 150 | |
| ❶ | Available nominal head of standard electric pump (TCAEY) | kPa | 106 | 87 | 113 | 102 | 87 | 74 |
| Electrical supply | V-ph-Hz | 400-3+N-50 | 400-3+N-50 | 400-3+N-50 | 400-3+N-50 | 400-3+N-50 | 400-3+N-50 | |
| DIMENSIONS AND WEIGHTS | 233 | 238 | 245 | 250 | 260 | 265 | ||
| L – Width | mm | 1710 | 2315 | 2315 | 2315 | 2315 | 2315 | |
| H – Height | mm | 1570 | 1570 | 1570 | 1570 | 1570 | 1570 | |
| P – Depth | mm | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | |
| ❹ | TCAEY weight | kg | – | 645 | 740 | 775 | 795 | 835 |
| ❹ | THAEY weight | kg | 500 | 660 | 760 | 795 | 815 | 855 |
| SEASONAL ENERGY PERFORMANCE | 233 | 238 | 245 | 250 | 260 | 265 | ||
| TCAEY MODEL SEASONAL PERFORMANCE IN COOLING MODE (P1 set up) | ||||||||
| ① | Pdesignc (EN 14825) | kW | – | 39,4 | 44,8 | 51,9 | 59,8 | 64,6 |
| ① | SEER (EN 14825) | – | 4,26 | 4,24 | 4,35 | 4,31 | 4,27 | |
| ② | ηs,c | % | – | 167 | 167 | 171 | 170 | 168 |
| THAEY MODEL SEASONAL PERFORMANCE IN HEATING MODE | ||||||||
| ③ | Pdesignh (EN 14825) | kW | 36 | 41 | 49 | 56 | 62 | 70 |
| ③ | SCOP (EN 14825) | 3,72 | 3,72 | 3,61 | 3,58 | 3,56 | 3,66 | |
| ④ | ηs | % | 146 | 146 | 141 | 140 | 140 | 144 |
| ④ | Energy class | A+ | A+ | A+ | A+ | A+ | A+ | |
- Data at the following conditions:
- ❶ Air: 35°C – Water: 12/7°C.
- ❷ Air: 7°C D.B. – 6°C W.B. – Water: 40/45°C.
- ❸ In open field (Q = 2) at 5 m from the unit.
- ❹ Weight refers to the most complete set up.
- Performance according to EN 14511
- ① Low temperature application (7°C)
- ② Seasonal energy efficiency: low temperature cooling (EU Regulation 2016/2281)
- ③ In Average climatic conditions, low temperature application (35°C)
- ④ Seasonal energy efficiency: low temperature heating in Average climate (EU Regulations No.811/2013 and No.813/2013)





Reviews