Dimensions W x L x H |
42.2 mm x 125.8 mm x 76.5 mm |
Width dimension |
18.9 mm |
CPU data |
128 MB RAMDual core 650 MHz |
Diagnostics via LED |
Force modeNetwork status, engineering port 1EtherCAT network statusRunPower supply for electronics/sensorsLoad power supplySystem fault |
Configuration support |
CODESYS V3 |
Max. number of modules |
10 |
Additional functions |
CODESYS V3 with SoftMotion |
System parameter |
Diagnostic memoryFail-safe responseSystem start |
Module parameters |
Channel alarm bundlingUndervoltage diagnosticsChannel alarms for undervoltageAnalog module process value representation |
Buffer time real-time clock |
3 Weeks |
Control elements |
DIL switch for RUN/STOP |
Processing time |
Approx. 200 µs/1 k instruction |
Intrinsic current consumption at nominal operating voltage for electronics/sensors |
Typically 65 mA |
IP address setting |
DHCPVia CODESYS |
Function blocks |
and othersRead CPX-E module diagnosticsCPX-E diagnostic statusCopying of CPX-E diagnostic trace |
Max. power supply |
8 A |
Flag |
120 kB remanent dataCODESYS variable concept |
Nominal operating voltage DC for electronics/sensors |
24 V |
Power failure buffering |
20 ms |
Programming software |
CODESYS provided by Festo |
Program memory |
12 MB user program |
Permissible voltage fluctuations for electronics/sensors |
± 25 % |
Power supply, function |
Electronics and sensors |
Power supply, type of connection |
Terminal strip |
Power supply, connection technology |
Spring-loaded terminal |
Power supply, number of pins/wires |
4 |
Power supply, connection pattern |
00995847 |
Power supply, conductor diameter |
0.2 mm² … 1.5 mm² |
Power supply, information on conductor diameter |
0.2 – 2.5 mm² for flexible conductors without cable end sleeves |
Certification |
RCM compliance markc UL us – Listed (OL) |
KC characters |
KC EMC |
CE marking (see declaration of conformity) |
As per EU EMC directive |
Certificate issuing authority |
UL E239998 |
Vibration resistance |
Transport application test with severity level 1 as per FN 942017-4 and EN 60068-2-6 |
Shock resistance |
Shock test with severity level 1 as per FN 942017-5 and EN 60068-2-27 |
Corrosion resistance class (CRC) |
0 – No corrosion stress |
Storage temperature |
-20 °C … 70 °C |
Relative air humidity |
95 %Non-condensing |
Protection against direct and indirect contact |
PELV |
Degree of protection |
IP20 |
Ambient temperature |
-5 °C … 50 °C |
Note on ambient temperature |
-5 – 60 °C for vertical installation |
Product weight |
145 g |
Max. address capacity outputs |
64 byte |
Max. address capacity inputs |
64 byte |
Fieldbus interface, galvanic isolation |
yes |
Fieldbus interface, transmission rate |
100 Mbit/s |
Fieldbus interface, type |
Ethernet |
Ethernet interface, connection type |
Socket |
Ethernet interface, connection technology |
RJ45 |
Ethernet interface, number of poles/wires |
8 |
Ethernet interface, transmission rate |
10 Mbit/s100 Mbit/s |
Ethernet interface, function |
Diagnostics |
Ethernet interface, protocol |
EasyIPModbus® TCPOPC-UATCP/IP |
Ethernet interface, connection pattern |
00995789 |
Fieldbus interface, function |
Bus connection, forwarding |
Fieldbus interface, connection type |
Socket |
Fieldbus interface, connection technology |
RJ45 |
Fieldbus interface, number of poles/wires |
8 |
Fieldbus interface, protocol |
EtherCAT Master |
Fieldbus interface, connection pattern |
00995789 |
Type of mounting |
With H-rail |
Note on materials |
Contains paint-wetting impairment substancesRoHS-compliant |
Housing material |
PA |
Reviews