Dimensions W x L x H |
18.9 mm x 76.6 mm x 124.3 mm |
Width dimension |
18.9 mm |
Diagnostics via LED |
Faults per moduleStatus per channel |
Diagnostics via bus |
Device missing/failedWire breakModule errorShort circuitParameter errorUnderflow/overflowUndervoltageGeneral error |
Module parameters |
Actuator supply short circuit diagnosticsDeactivate sensor supplyResponse to short circuit/overload |
Channel parameters |
Deactivate actuator supplyDevice fault codeForcing channel xChannel modeChannel statusCycle time |
Fuse protection (short circuit) |
Internal electronic fuse, load per channelInternal electronic fuse, sensor per module |
Intrinsic current consumption at nominal operating voltage for electronics/sensors |
Typically 50 mA |
Intrinsic current consumption at nominal operating voltage load |
Typically 15 mA |
Nominal operating voltage DC for electronics/sensors |
24 V |
Nominal operating voltage DC load |
24 V |
Electrical isolation between channel and internal bus |
no |
Electrical isolation between channels |
no |
Permissible voltage fluctuations for electronics/sensors |
± 25 % |
Permissible voltage fluctuations load |
± 25 % |
Power supply, type of connection |
Terminal strip |
Power supply, connection technology |
Spring-loaded terminal |
Power supply, number of pins/wires |
4 |
Power supply, connection pattern |
00995847 |
Power supply, conductor diameter |
0.2 mm² … 1.5 mm² |
Power supply, information on conductor diameter |
0.2 – 2.5 mm² for flexible conductors without cable end sleeves |
Certification |
RCM compliance markc UL us – Listed (OL) |
KC characters |
KC EMC |
CE marking (see declaration of conformity) |
As per EU EMC directive |
Certificate issuing authority |
UL E239998 |
Vibration resistance |
Transport application test with severity level 1 as per FN 942017-4 and EN 60068-2-6 |
Shock resistance |
Shock test with severity level 1 as per FN 942017-5 and EN 60068-2-27 |
Corrosion resistance class (CRC) |
0 – No corrosion stress |
Storage temperature |
-20 °C … 70 °C |
Relative air humidity |
95 %Non-condensing |
Protection against direct and indirect contact |
PELV |
Degree of protection |
IP20 |
Ambient temperature |
-5 °C … 50 °C |
Note on ambient temperature |
-5 – 50 °C for horizontal installation |
Product weight |
96 g |
Protocol |
IO-Link® |
IO-Link®, protocol version |
Master V 1.1 |
IO-Link®, communication mode |
Configurable via softwareSIO, COM1 (4.8 kBd), COM2 (38.4 kBd), COM3 (230.4 kBd) |
IO-Link®, port class |
B |
IO-Link®, number of ports |
4 |
IO-Link®, process data width OUT |
8–32 bytes parameterizable |
IO-Link®, process data width IN |
8–32 bytes parameterizable |
IO-Link®, minimum cycle time |
Depends on minimally supported cycle time of connected IO-Link® device |
IO-Link®, communication |
C/Q LED green |
Electrical IO-Link® connection, connection type |
4x terminal strip |
Electrical connection, IO-Link®, connection technology |
Spring-loaded terminal |
Electrical IO-Link® connection, number of pins/wires |
6 |
Electric IO-Link® connection, connection pattern |
00995843 |
IO-Link® electrical connection, conductor cross section |
0.2 mm² … 1.5 mm² |
IO-Link® electrical connection, information on conductor cross section |
0.2 – 2.5 mm² for flexible conductors without cable end sleeves |
Type of mounting |
With H-rail |
Note on materials |
Contains paint-wetting impairment substancesRoHS-compliant |
Housing material |
PA |
Reviews