Description
Description
Construction features
• Compressor: scroll type, rotary, hermetic with Inverter actuation, complete with thermal protection and casing heater.
• Water side heat exchanger: adequately insulated stainless steel plates, complete with antifreeze heater and water flow differential pressure switch.
• Air side heat exchanger: featuring finned coil with copper pipes and aluminium fins for TCAITY with hydrophilic treatment for THAITY, complete with protection grilles.
• Fan: external rotor axial type electric fans equipped with internal thermal protection, accident protection grilles and proportional electronic device for continuous fan rotation speed regulation.
• Control: microprocessor electronic control with Adaptive Function Plus logic.
• Structure: made of galvanised and painted steel plate, complete with condensate drain pan and unit base antifreeze heater for THAITY.
• The unit is also complete with:
– outdoor air temperature probe for set-point compensation;
– electronic expansion valve;
– display of cooling circuit high and low pressure;
– Master/Slave control up to 4 units in parallel;
– clock board.
Version
T – High efficiency.
Models
TCAITY: unit designed for cooling only.
THAITY: heat pump unit.
PUMP set-up
• Pump unit complete with: EC circulator with 3 speed selector or continuous speed regulation or electric pump, membrane expansion tank, manual air vent valve, safety valve and pressure gauge.
TANK&PUMP set up
• Pump unit complete with: inertial buffer tank, circulator or electric circulation pump, membrane expansion tank, manual air vent valve, safety valve, and pressure gauge.
Factory fitted accessories
• Forced Download. Compressor partialisation or switch-off to limit power and current consumption (digital input).
• Condensing control with fans with EC motor.
• Silenced set up.
• Antifreeze heater on the tank.
• Circulator/electric pump antifreeze heater.
• Pre-painted copper/coils or copper/copper coils.
• Digital input for double set-point.
• 4-20 mA analogue signal for shifting set-point.
• Low water set-point temperature.
Separately supplied accessories
• 3-way valve for the production of domestic hot water, managed by regulation.
• Additional electrical resistance for heat pump, managed by regulation.
• Remotable outdoor air temperature probe for compensation of the set-point.
• Water filter.
• Rubber anti-vibration mounts.
• Remote keypad with display.
• Interfaces for serial communication with other devices.
• RS485/USB serial converter.
• Rhoss supervisors for unit monitoring and remote management.
Technical data
| TCAITY MODEL | 120 | 125 | 130 | ||
| ❶ | Cooling capacity | kW | 18,8 | 25,2 | 29,3 |
| ❶ | Absorbed power | kW | 6,53 | 8,72 | 10,17 |
| ❶ | E.E.R. | 2,88 | 2,89 | 2,88 | |
| THAITY MODEL | 120 | 125 | 130 | ||
| ❷ | Heating capacity | kW | 20 | 25,6 | 30,4 |
| ❷ | Absorbed power | kW | 6,15 | 7,83 | 9,5 |
| ❷ | C.O.P. NOM | 3,25 | 3,27 | 3,2 | |
| ❸ | Heating capacity | kW | 21,1 | 26,1 | 30,7 |
| ❸ | Absorbed power | kW | 5,2 | 6,41 | 7,62 |
| ❸ | C.O.P. | 4,06 | 4,07 | 4,03 | |
| ❹ | Heating capacity | kW | 14,8 | 18,1 | 21,3 |
| ❹ | Absorbed power | kW | 4,92 | 6,51 | 7,61 |
| ❹ | C.O.P. | 3,01 | 2,78 | 2,8 | |
| ❶ | Cooling capacity | kW | 18,5 | 24,1 | 28,3 |
| ❶ | E.E.R. | 2,7 | 2,75 | 2,71 | |
| TCAITY-THAITY MODEL | 120 | 125 | 130 | ||
| ❺ | Sound pressure | dB(A) | 47 | 50 | 51 |
| ❶ | P0 circulator available head | kPa | 77 | 80 | 67 |
| Buffer tank water content | l | 110 | 110 | 110 | |
| Electrical supply | V-ph-Hz | 400-3+N-50 | 400-3+N-50 | 400-3+N-50 | |
| DIMENSIONS AND WEIGHT | 120 | 125 | 130 | ||
| L – PUMP width | mm | 1522 | 1522 | 1522 | |
| L – TANK&PUMP width | mm | 1625 | 1625 | 1625 | |
| H – PUMP height | mm | 1280 | 1280 | 1280 | |
| H – TANK&PUMP height | mm | 1590 | 1590 | 1590 | |
| P – PUMP Depth | mm | 600 | 600 | 600 | |
| P – TANK&PUMP Depth | mm | 600 | 600 | 600 | |
| ❻ | PUMP Weight | kg | 245 | 265 | 275 |
| ❻ | TANK&PUMP Weight | kg | 345 | 365 | 375 |
| SEASONAL ENERGY PERFORMANCE | 120 | 125 | 130 | ||
| TCAITY MODEL SEASONAL PERFORMANCE IN COOLING MODE | |||||
| ① | Pdesignc (EN 14825) | kW | 18,8 | 25,2 | 29,3 |
| ① | SEER (EN 14825) | 4,31 | 4,36 | 4,32 | |
| ② | ηs,c | % | 169 | 171 | 170 |
| THAITY MODEL SEASONAL PERFORMANCE IN HEATING MODE – Low temperature application 35°C | |||||
| ③ | Pdesignh (EN 14825) | kW | 21 | 26 | 30 |
| ③ | SCOP (EN 14825) | 4,17 | 3,63 | 3,88 | |
| ④ | ηs | % | 164 | 142 | 152 |
| ④ | Energy class | A++ | A+ | A++ | |
| THAITY MODEL SEASONAL PERFORMANCE IN HEATING MODE – Medium temperature application 55°C | |||||
| ③ | Pdesignh (EN 14825) | kW | 19 | – | – |
| ③ | SCOP (EN 14825) | 3,41 | – | – | |
| ④ | ηs | % | 133 | – | – |
| ④ | Energy class | A++ | – | – | |
- Data at the following conditions:
- ❶ Air: 35°C D.B. – Water: 12/7°C.
- ❷ Air: 7°C D.B. – 6°C W.B. – Water: 40/45°C.
- ❸ Air: 7°C D.B. – 6°C W.B. – Water: 30/35°C.
- ❹ Air: -7°C D.B. – Water: 30/35°C.
- ❺ In open field (Q = 2) at 5 m from the unit.
- ❻ Weight refers to the most complete setup.
- Performance according to EN 14511. P0 setup.
- ① Low temperature application (7°C)
- ② Seasonal energy efficiency: low temperature cooling (EU Regulation 2016/2281)
- ③ In Average climatic conditions.
- ④ Seasonal energy efficiency: ambient heating in Average climate (EU Regulations No.811/2013 and No.813/2013)





Reviews