Description
Application
| Application | Flow monitoring; Wire monitoring |
|---|
Electrical data
| Frequency AC [Hz] | 47…63 |
|---|---|
| Operating voltage tolerance [%] | -10…10 |
| Operating voltage [V] | < 200 AC |
| Max. power consumption [VA] | 5 |
| Reverse polarity protection | no |
| Power-on delay time [s] | 30 |
| Number of channels | 1 |
Outputs
| Electrical design | relay |
|---|---|
| Contact rating | 4 A (250 V AC cos phi > 0,7) ; 0,2 A (250 V DC); 4 A (24 V DC) |
| Switching function flow monitoring | relay energised when flow is present |
| Switching function wire break monitoring | relay de-energised in case of wire break |
| Short-circuit proof | no |
| Overload protection | no |
Software / programming
| Adjustment of the switch point | potentiometer |
|---|---|
| Selection liquids / gases | slide switch |
Operating conditions
| Ambient temperature [°C] | -20…60 |
|---|---|
| Storage temperature [°C] | -20…85 |
| Protection | IP 40 |
| Protection rating terminals | IP 20 |
Tests / approvals
| Approval | PTB 01 ATEX 2075; TIIS TC16593 |
|---|---|
| ATEX marking | |
| MTTF [years] | 248 |
Mechanical data
| Weight [g] | 548.5 |
|---|---|
| Housing | housing for DIN rail mounting |
| Dimensions [mm] | 78 x 45 x 120 |
| Materials | plastics |
Displays / operating elements
| Display |
|
|---|
Electrical connection
| Required protection | miniature fuse to IEC60127-2 sheet 1; ≤ 5 A; fast acting; Place the fuse outside the hazardous area. |
|---|
Remarks
| Remarks |
|
||
|---|---|---|---|
| Pack quantity | 1 pcs. |
Electrical connection
| Connection | terminals: 15 x …2.5 mm² |
|---|
Other data
Maximum values for control circuit
| in protection rating intrinsic safety | [EEx ia] IIC | [EEx ia] IIB | [EEx ib] IIC | [EEx ib] IIB |
| Voltage [V] | 15.8 | 15.8 | 15.8 | 15.8 |
| Current [mA] | 92 | 92 | 92 | 92 |
| Power [mW] | 680 | 680 | 680 | 680 |
| External inductance [mH] | 1 | 1 | 1 | 1 |
| External capacitance [µF] | 0.185 | 1.6 | 0.185 | 1.6 |






Reviews