Test and Drainage Valves

In sprinkler systems, these valves are used for the testing systems and drain the unnecessary fluids from the systems.

Advantages: They have sight glasses in their body,single valve is sufficient to drain the line.

For choosing the test and drain valves, users should pay attention to line diameter. Also these valves have to have same diameter with the sprinkler orifice diameter.

ID:1368117

Description

Table 8.16.2.4.2. – NFPA13

Line diameter (in)                    Test and drain Valve diameter (in)
 2” and under   ¾” and over
 2 ½”, 3”, 3 ½”  1 ¼” and over
 4” and over  2″

 

Connection Type:
Threaded or Grooved

Working Pressure:
300psi

Diameters:
1” – 2”

K Orifice
k: 80, k: 115, k: 160, k: 200, k: 242, k: 320, k: 360

Material Features:
 
Body: Brass
 Ball and disc: Chromed
 
Gasket: Teflon

Application areas:
These are suitable for the system where has sprinkler systems.

Approvals:
– UL Listed
– ULc Listed 
– FM Approved