Description
Description
Construction features
• Compressor: scroll type, rotary, hermetic complete with thermal protection and casing heater.
• 4 capacity steps with high efficiency at partial loads.
Water side heat exchanger: with stainless steel plates, complete with closed cell polyurethane foam rubber insulation and water flow differential pressure switch.
• Air side heat exchanger: with micro-channels.
• Fan: external rotor axial type electric fans with internal thermal protection, accident protection grilles.
• Control: microprocessor electronic control with Adaptive Function Plus logic.
• Structure: load-bearing structure made of galvanised and painted steel plate with polyester powder coating.
• The unit is also complete with:
– fan and compressor circuit breaker switches;
– display of cooling circuit high and low pressure;
– Master/Slave control up to 4 units in parallel;
– clock board;
– control of Variable Primary Flow (VPF_R).
Versions
• B – Standard version.
• S – Silenced version complete with compressor technical compartment soundproofing and reduced speed fans.
Models
• TCAEBY: standard unit designed for cooling only.
• TCAESY: silenced unit designed for cooling only.
Factory fitted accessories
• Shell and tube evaporator.
• PUMP with single or double electric pump, one of which automatic in standby. The electric pumps are available in the low or high head versions.
• TANK&PUMP with 500 – 700 litre integrated buffer tank (depending on models) and single or double electric pump, complete with expansion tank, air vent valves, safety valve and water side pressure gauge.
• Inverter pump control for unit start-up.
• Desuperheater.
• 100% heat recovery unit.
• Electronic expansion valve.
• Condensing control (standard in S versions).
• Condensing control with fans with EC motor.
• Condensing control with over-pressure fans.
• Power factor correction capacitors (cosφ > 0.94).
• Forced limit of power consumption.
• Forced noise limit.
• Energy parameter measuring device.
• Optimised energy efficiency.
• Soft starter.
• Soundproofed compressor box.
• Compressor soundproof enclosures.
• Cooling circuit outlet and inlet valves.
• Refrigerant leak detector.
• Cooling circuit high and low pressure gauges.
• Double safety valves.
• Coil protection nets.
• Micro-channel coils with E-coating treatment.
• Control of min/max power supply voltage.
• Digital input for double set-point.
• 4-20 mA analogue signal for shifting set-point.
• Evaporator antifreeze heater, electrical panel, buffer tank, electric pumps and heat exchangers for heat recovery, if applicable.
• Low temperature water production.
• Interfaces for serial communication with other devices.
• Anti-vibration mounts.
Separately supplied accessories
• Remote keypad with display.
• Thermostat with display.
• Rhoss supervisors for unit monitoring and remote management.
• Rhoss sequencer for integrated management of multiple chillers.
Technical data
| TCAEBY-TCAESY MODEL | 4225 | 4245 | 4265 | 4315 | 4345 | ||
| ❶ | Nominal cooling capacity | kW | 220,2 | 241,2 | 264 | 313,9 | 345,7 |
| ❶ | Nominal cooling capacity | kW | 214,2 | 234,2 | 252,1 | 305 | 333,8 |
| ❶ | E.E.R. | 3 | 2,81 | 2,61 | 2,88 | 2,81 | |
| ❶ | E.E.R. | 2,9 | 2,67 | 2,4 | 2,76 | 2,66 | |
| ❶ | Absorbed power | kW | 73,4 | 85,8 | 101,1 | 108,9 | 123 |
| ❶ | Absorbed power | kW | 73,9 | 87,7 | 105 | 110,5 | 125,5 |
| TCAEBY-TCAESY MODEL | 4225 | 4245 | 4265 | 4315 | 4345 | ||
| ❷ | Sound pressure | dB(A) | 58 | 59 | 60 | 61 | 62 |
| ❷ | Sound pressure | dB(A) | 52 | 53 | 54 | 56 | 57 |
| ❸ | Sound power | dB(A) | 90 | 91 | 92 | 93 | 94 |
| ❸ | Sound power | dB(A) | 84 | 85 | 86 | 88 | 89 |
| Scroll compressors/steps | n. | 4/4 | 4/4 | 4/4 | 4/4 | 4/4 | |
| Circuits | n. | 2 | 2 | 2 | 2 | 2 | |
| Electrical supply | V-ph-Hz | 400-3-50 | 400-3-50 | 400-3-50 | 400-3-50 | 400-3-50 | |
| DIMENSIONS AND WEIGHTS | 4225 | 4245 | 4265 | 4315 | 4345 | ||
| L – Width | mm | 2550 | 2550 | 2550 | 3650 | 3650 | |
| H – Height | mm | 2450 | 2450 | 2450 | 2450 | 2450 | |
| P – Depth | mm | 2260 | 2260 | 2260 | 2260 | 2260 | |
| ❹ | TCAEBY weight | kg | 1300 | 1500 | 1650 | 1985 | 2000 |
| ❹ | TCAESY weight | kg | 1460 | 1660 | 1810 | 2215 | 2230 |
| SEASONAL ENERGY PERFORMANCE | 4225 | 4245 | 4265 | 4315 | 4345 | ||
| TCAEBY MODEL SEASONAL PERFORMANCE IN COOLING MODE | |||||||
| ① | Pdesignc (EN 14825) | kW | 220,2 | 241,2 | 264 | 313,9 | 345,7 |
| ① | SEER (EN 14825) | 4,31 | 4,31 | 4,3 | 4,34 | 4,34 | |
| ② | ηs,c | % | 169 | 169 | 169 | 170 | 171 |
| TCAESY MODEL SEASONAL PERFORMANCE IN COOLING MODE | |||||||
| ① | Pdesignc (EN 14825) | kW | 214,2 | 234,2 | 252,1 | 305 | 333,8 |
| ① | SEER (EN 14825) | 4,28 | 4,27 | 4,26 | 4,3 | 4,3 | |
| ② | ηs,c | % | 168 | 168 | 167 | 169 | 169 |
- Data at the following conditions:
- ❶ Air: 35°C – Water: 12/7°C.
- ❷ In open field (Q = 2) at 10 m from the unit.
- ❸ Total sound power level in dB(A) based on measurements carried out in accordance with regulation UNI EN-ISO 9614.
- ❹ Weight referred to the unit without load and not accessorised.
- ■ TCAESY silenced versions
- Performance according to EN 14511.
- ① Low temperature application (7°C)
- ② Seasonal energy efficiency: low temperature cooling (EU Regulation 2016/2281)