Description
Electrical data
| Frequency AC [Hz] | 47…64 | |
|---|---|---|
| Operating voltage tolerance [%] | 10 | |
| Operating voltage [V] | automatic range selection | |
| Nominal voltage AC [V] | 110 / 230 | |
| Input voltage range AC [V] | 100…120 / 200…240 | |
| Protection class | I | |
| Overvoltage protection | yes; (< 36 V) | |
| Max. power-on delay time [ms] | 900 | |
| Output voltage AS-i [V] | 30.5 | |
| Output power (permanent) [W] | 122 | |
| Output power (peak) [W] | 134 | |
| Note on output power (peak) [W] |
|
|
| Power factor (nominal voltage 120 V AC / 60 Hz) | 0.56 | |
| Power factor (nominal voltage 230 V AC / 50 Hz) | 0.47 | |
| Power reserve [%] | 10 | |
| Number of output circuits | 1 | |
| Output current AS-i [A] | 4 | |
| Max. residual ripple [mV] | 50 | |
| Switch-on peak current (nominal voltage 120 V AC / 60 Hz) [A] | 3 | |
| Switch-on peak current (nominal voltage 230 V AC / 50 Hz) [A] | 3 | |
| Inrush current limitation | yes | |
| Efficiency (nominal voltage 120 V AC / 60 Hz) [%] | 88 | |
| Efficiency (nominal voltage 230 V AC / 50 Hz) [%] | 89.3 | |
| External input protection | ≤ B-10 A / ≤ C-6 A | |
| Derating [W/K] | 3 (60…70 °C) | |
| Mains buffering time (nominal voltage 120 V AC / 60 Hz) [ms] | 70 | |
| Mains buffering time (nominal voltage 230 V AC / 50 Hz) [ms] | 70 | |
| Input current (nominal voltage 120 V AC / 60 Hz) [A] | 2.05 | |
| Input current (nominal voltage 230 V AC / 50 Hz) [A] | 1.23 | |
| Power loss (nominal voltage 120 V AC / 60 Hz) [W] | 16.6 | |
| Power loss (nominal voltage 230 V AC / 50 Hz) [W] | 14.6 | |
| Integrated data decoupling | yes | |
| Back feeding protection [V] | 35 |
Outputs
| Short-circuit proof | yes |
|---|---|
| Overload protection | yes |
| Overload performance | output current constant |
| Parallel connection of outputs possible | no |
| Series connection of outputs possible | no |
Operating conditions
| Ambient temperature [°C] | -25…70 | |
|---|---|---|
| Note on ambient temperature |
|
|
| Storage temperature [°C] | -40…85 | |
| Max. relative air humidity [%] | 95; (IEC 60068-2-30) | |
| Protection | IP 20 | |
| Pollution degree | 2; (IEC 62103: conductive soiling not permitted) |
Tests / approvals
| EMC |
|
||||||
|---|---|---|---|---|---|---|---|
| Vibration resistance |
|
||||||
| Shock resistance |
|
||||||
| MTTF [years] | 90 |
AS-i classification
| AS-i certificate | 98601 |
|---|
Mechanical data
| Weight [g] | 625.5 |
|---|---|
| Type of mounting | rail; (TH35 (EN 60715)) |
| Dimensions [mm] | 124 x 40 x 120 |
| Materials | steel sheet |
Displays / operating elements
| Display |
|
|---|
Remarks
| Pack quantity | 1 pcs. |
|---|
Electrical connection
| Connection | screw terminals: |
|---|










Reviews