AC2750

  • For installation in small housings, control cabinets and operator panels
  • Simple and fast wiring by means of wire strands
  • Particularly space-saving design
  • For integration of mechanical switches into AS-i networks
  • AS-i connection for four control and signalling devices

 

SKU: AC2750

$126,30

Description

Application
Design only for operation with AS-i masters with the profile M4
Application housing for panel mounting
Electrical data
Operating voltage [V] 18…31.6 DC
Max. current consumption from AS-i [mA] 180; (without sensors: < 30 mA; inputs and outputs active: < 180 mA)
Protection class III
Max. current load total [A] 0.15; (total current for all inputs and outputs supplied from AS-i: 150 mA)
Integrated watchdog yes
Inputs / outputs
Number of inputs and outputs Number of digital inputs: 4; Number of digital outputs: 4
Inputs
Number of digital inputs 4
Input circuit of digital inputs PNP
Sensor supply of the inputs AS-i
Power supply [V] 18…30; (DC)
Max. total current rating of inputs [mA] 150
Input current High [mA] 6…10
Input current Low [mA] 0…2
Switching level high [V] > 11
Digital inputs protected against short circuits yes
Outputs
Electrical design PNP
Number of digital outputs 4
Circuit PNP
Voltage range DC [V] 18…30; (DC)
Max. current load per output [mA] 100; (utilisation category DC-13 (control of electromagnets): 2,5 W (IEC 60947-5-1))
Max. current load outputs total [A] 0.15
Short-circuit proof yes
Electrically separated yes
Actuator supply outputs AS-i
Operating conditions
Ambient temperature [°C] -25…55
Protection IP 20
Tests / approvals
EMC
EN 50295
AS-i classification
AS-i version 3.0
Extended addressing mode yes
AS-i profile S-7.A.7
AS-i I/O configuration [hex] 7
AS-i ID code [hex] A.7
AS-i certificate 102301
Mechanical data
Weight [g] 75.5
Type of mounting installation in a surface-mounted housing
Dimensions [mm] 31.1 x 12 x 76.6
Materials housing: PC potted
Displays / operating elements
Display
operation LED, green
errors LED, red
function LED, yellow
Remarks
Remarks
A watchdog function switches the outputs off if there is no communication on the AS-i line.
Install the unit so that exposed parts cannot be touched.
Installation in a surface-mounted housing with the dimensions of 68 x 136 x 53 mm (LxWxH), e.g. Schneider Electric Harmony, XALD03, XALD04
Do not connect any of the following points to an external potential:
0-, I+, I1, I2, I3, I4
The connections are electrically connected with the AS-i cable.
can be used up to a height of 2000 metres above sea level
Pack quantity 1 pcs.
Electrical connection
Cable: 0.2 m, PVC

 

PDF data sheet

Reviews

There are no reviews yet.

Be the first to review “AC2750”

Your email address will not be published. Required fields are marked *