Description
Product characteristics
| Number of inputs and outputs | Number of digital outputs: 2 | ||||
|---|---|---|---|---|---|
| Measuring range |
|
||||
| Process connection | threaded connection G 1/4 internal thread |
Application
| Special feature | Gold-plated contacts | |||
|---|---|---|---|---|
| Application | for industrial applications | |||
| Media | liquids and gases | |||
| Medium temperature [°C] | -20…60 | |||
| Min. bursting pressure |
|
|||
| Pressure rating |
|
|||
| Type of pressure | relative pressure |
Electrical data
| Operating voltage [V] | 18…36 DC; (to SELV/PELV) |
|---|---|
| Current consumption [mA] | < 50 |
| Protection class | III |
| Reverse polarity protection | yes |
| Overvoltage protection | yes; (< 40 V) |
| Power-on delay time [s] | 0.3 |
| Integrated watchdog | yes |
Inputs / outputs
| Number of inputs and outputs | Number of digital outputs: 2 |
|---|
Outputs
| Total number of outputs | 2 |
|---|---|
| Output signal | switching signal; IO-Link; (configurable) |
| Electrical design | PNP/NPN |
| Number of digital outputs | 2 |
| Output function | normally open / normally closed; (parameterisable) |
| Max. voltage drop switching output DC [V] | 2 |
| Permanent current rating of switching output DC [mA] | 250 |
| Switching frequency DC [Hz] | < 170 |
| Short-circuit protection | yes |
| Type of short-circuit protection | pulsed |
Measuring/setting range
| Measuring range |
|
||||||
|---|---|---|---|---|---|---|---|
| Set point SP |
|
||||||
| Reset point rP |
|
||||||
| In steps of |
|
||||||
| Factory setting |
|
Accuracy / deviations
| Switch point accuracy [% of the span] | < ± 0,5 |
|---|---|
| Repeatability [% of the span] | < ± 0,1; (with temperature fluctuations < 10 K) |
| Characteristics deviation [% of the span] | < ± 0,25 (BFSL) / < ± 0,5 (LS); (BFSL = Best Fit Straight Line; LS = limit value setting) |
| Hysteresis deviation [% of the span] | < ± 0,25 |
| Long-term stability [% of the span] | < ± 0,05; (per 6 months) |
| Temperature coefficient zero point [% of the span / 10 K] | 0,2; (0…60 °C) |
| Temperature coefficient span [% of the span / 10 K] | 0,2; (0…60 °C) |
Response times
| Delay time programmable dS, dr [s] | 0; 0,2…50 |
|---|
Software / programming
| Parameter setting options | hysteresis / window; normally open / normally closed; diagnostic function; switching logic; switch-on/switch-off delay; Damping; Display unit |
|---|
Interfaces
| Communication interface | IO-Link | ||||
|---|---|---|---|---|---|
| Transmission type | COM2 (38,4 kBaud) | ||||
| IO-Link revision | 1.1 | ||||
| SDCI standard | IEC 61131-9 CDV | ||||
| Profiles | no profile | ||||
| SIO mode | yes | ||||
| Required master port type | A | ||||
| Process data analogue | 1 | ||||
| Process data binary | 2 | ||||
| Min. process cycle time [ms] | 2.3 | ||||
| Supported DeviceIDs |
|
Operating conditions
| Ambient temperature [°C] | -20…60 |
|---|---|
| Storage temperature [°C] | -40…100 |
| Protection | IP 65 |
Tests / approvals
| ATEX marking | |||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| EMC |
|
||||||||||
| Shock resistance |
|
||||||||||
| Vibration resistance |
|
||||||||||
| MTTF [years] | 194 | ||||||||||
| Pressure Equipment Directive | Sound engineering practice; can be used for group 2 fluids; group 1 fluids on request |
Mechanical data
| Weight [g] | 303 |
|---|---|
| Materials | stainless steel (1.4301 / 304); stainless steel (1.4404 / 316L); PC; PBT; PEI; FKM; PTFE |
| Materials (wetted parts) | stainless steel (1.4305 / 303); ceramics; FKM |
| Min. pressure cycles | 100 million |
| Process connection | threaded connection G 1/4 internal thread |
| Restrictor element integrated | no (can be retrofitted) |
Displays / operating elements
| Display |
|
|---|
Remarks
| Pack quantity | 1 pcs. |
|---|
Electrical connection
| Connector: 1 x M12; coding: A; Contacts: gold-plated |